Foam Maker is used for one of the most common applications of protecting tank seal in vertical liquid storage tank with internal floating roof with low expansion foam system. The application of aspirated foam is on the basis of the risk comprising the area in the annular ring between the rim of the floating roof and the tank shell. The Foam system design guidelines generally used are in accordance with NFPA11 standard. The Foam Makers are defined by NFPA 11 as Type II discharge outlets for delivering the low expansion aspirated foam to the seal. The Foam Makers are widely used with the Inline Foam Inductor, Balance Pressure Foam Proportioning system, Bladder Tank system and Foam tenders.
Model No. | Material | Inlet Size | Flow Rate (LPM) | |
---|---|---|---|---|
as per UL | as per FM | |||
NF-FM50 | Carbon Steel | 65 NB | 72 – 335 | 89 – 378 |
NF-FMSS50 | Stainless Steel | |||
NF-FM65 | Carbon Steel | 65 NB | 150 – 550 | 155 – 549 |
NF-FMSS65 | Stainless Steel |